- - CL340
AC 40M/400M/400A
Á¦Á¶»ç : YOKOGAWA
Á¦Ç°¸í : CLAMP METERS
Á¦Ç°¹øÈ£ : CL340
Á¦Ç°ºÐ·ù : Ŭ·¥ÇÁ¹ÌÅÍ
Á¦Ç°»ó¼¼Á¤º¸
| Description | Leakage Current Mini Clamp-on |
|---|---|
| Method of detection | Mean Value |
| Display | LCD (Digital display: 3999 counts) |
| Response Time | Approx. 2 seconds |
| Range Switching | Manual-range |
| Data hold | On all range |
| Operating temperature and humidity | 0 - 40°C, 85% RH or less (no condensation) |
| Influence of external magnetic field | 10 mA or less in proximity to a 15 mm-dia conductor carrying 100A |
| Influence of conductor position | 40/400 mA range: Within 5 dgt at every part inside the jaw400A range, 0 to 250A:Within ±0.5% rdg ±5 dgt at every part inside the jaw section |
| Influence of Residual Current | 12 mA or less in proximity to a 10 mm-dia conductor carrying 100A |
| Safety Standard | Conforms EN61010-1, EN61010-2-032 |
| Circuit voltage | 300 Vrms or less |
| Withstanding voltage | 3.7 kV AC for one minute |
| Power Supply | LR03 x 2 R0-3(UM-4) x 2 |
| Battery Life | Approx. 40 hours (continuous) |
| Consumed current | Approx. 13 mA |
| Auto power-off | Approx. 10 minutes |
| Diameter of measurable conductor | 40 mm at maximum |
| Dimensions | Approx. 81 (W) x 185 (H) x 40 (D) mm |
| Weight | Approx. 270 g |
| Accessories | Batteries, carrying case (93030) User''s manual (IM CL340) |
| Peak Hold | On all range |
 
Selection Guide
| DC Current Range | - |
|---|---|
| DC Current Resolution | - |
| AC Current Range | 40/400mA,400A |
| AC Current Resolution | 0.01mA |
| AC Current Frequency characteristics | 20~1kHz |
| AC Current Method of detection | Mean Value |
| AC Voltage Measurement | - |
| DC Voltage Measurement | - |
| Continuity Check Measurement | - |
| Frequency Measurement | - |
| Temperature Measurement | - |
| Recorder output Function | - |
| Waveform monitor output Function | - |
| Data hold Function | O |
| Auto hold Function | - |
| Peak Hold Function | O |
| Maximum value memory Function | - |
| Mean value display Function | - |
| Filter Function | O |
| Range Hold Function | O |
| Auto ZERO Adjust Function | - |
| Auto power-off Function | O |
 
Additional Specification
At 23°C±5°C£¬75%RH or less
Accuracy: ±( % rdg dgt) = ±(% readout value of least significant digit)
| Parameter | Reference | Accuracy | |
|---|---|---|---|
| WIDE (20Hz¢¦) | 50/60Hz | ||
| AC current | 40mA/400mA | 2.510 (20¢¦1kHz) | 1.05 (50/60Hz) |
| 400A(0¢¦350A) | 2.510 (40¢¦1kHz) | 1.05 (50/60Hz) | |
| 400A(350¢¦400A) | 5.0 (40¢¦1kHz) | 2.0 (50/60Hz) | |


Á¦Ç°Á¤º¸
¡Ü MEAN VALUE DISPLAY
¡Ü AUTO POWER-OFF
¡Ü MANUAL RANGE SWITCHING
¡Ü APPROVED FOR COMFORMITY TO SAFETY STANDARDS EN61010-1, EN61010-2-032 (CAT. III 300 V)